The safety relay monitors emergency stop switches, safety switches and AOPDs. In spite of its installation width spanning just 22,5 mm, it offers space for switching status displays and attaching an operating equipment label.

Features at a Glance

  • Installation width just 22,5 mm
  • Clear terminal assignment thanks to coding pins
  • Circuit diagram directly on the housing
  • Optional cross-circuit monitoring
  • 0.1…30 s off-delay

Technical Data

Electrical Data

Supply Voltage 20.4 … 28.8 V DC
Supply Voltage 20.4 … 26.4 V AC
Input wiring 1-, 2-channel
Response time (automatic start) 120 ms
Response time (monitored start) 25 ms
Fall time (emergency stop) < 20 ms
Off-Delay 0.1 … 30 s
Temperature Range -25 … 60 °C
Storage temperature -40 … 85 °C
Number of Safety Outputs stop 0 2
Number of Safety Outputs stop 1 1
Switching current safety output (250 V AC) 8 A
Number of Signal Outputs 1
Switching current signal output (24 V DC 100 mA

Mechanical Data

Housing Material Plastic
Degree of Protection IP20
Connection Screw Clamp (pluggable)
Clampable Wire Cross-Section 0.2 … 2.5 mm²
DIN-Rail mounting 35 mm
Weight 314 g

Safety-relevant Data

Performance Level (EN ISO 13849-1), Stop 0 up to Cat. 4 PL e
Performance Level (EN ISO 13849-1), Stop 1 up to Cat. 3 PL d
Mission Time TM (EN ISO 13849-1) 20 a
Safety integrity level (EN 61508) Stop 0 up to SIL 3
Safety integrity level (EN 61508) Stop 1 up to SIL 2
Stop Category (EN 60204-1) 0 / 1
B10d Switching Cycles (mechanical) 20 000 000
B10d Switching Cycles (40 % load) 7 500 000
B10d Switching Cycles (60 % load) 2 500 000
B10d Switching Cycles (80 % load) 1 000 000
B10d Switching Cycles (100 % load) 400 000

General Data

Scope of delivery 1 × coding pin
1 × quick start
1 × screw terminal
1 × safety relays

Function

Cross-circuit detection optional
Start, monitored yes
Start, automatically yes
Contactor Monitoring yes
Input signal NC yes
Input signal OSSD yes

Standards and certificates

Connection Table

Ctrl. Panel

68 = Power LED
71 = Channel 1
87 = Channel 2
89 = Internal operating voltage