P1XD212 Fiber-optic amplifier
Fiber-Optic Amplifier
Applications: Sensors & I/O
Description
Fiber-optic sensors work according to the energetic principle in which light is emitted via one fiber-optic cable and received via another. The amplifier can be adapted to a wide range of application requirements through the use of flexible plastic fiber-optic cables or glass fiber-optic cables with adapter no. 7. The display shows the switching threshold as well as the currently received signal, which allows the sensor to be set up quickly and intuitively using the buttons. More complex parameterizations can be conveniently carried out via the wenglor weCon app on a mobile device or via IO-Link. P1XD200 series sensors can be operated in stand-alone and in multi-unit operation with up to 14 additional sensors. Despite closely positioned queries, there is no mutual influence in multi-unit operation. All sensor information is also provided via the IO-Link process data. Both the fiber-optic cable and the amplifier can be mounted without tools, which further simplifies handling.
Features at a Glance
- Tool-free assembly
- Intuitive setup using display
- NFC communication via the weCon app and IO-Link
- Blue and red LED light in one device, increased range with pink light
- Stand-alone and multi-unit operation (14 sensors) possible
Technical Data
Optical Data
| Light Source | Bi-Color |
| Service Life (T = +25 °C) | > 100,000 h |
| Max. Ambient Light | 10,000 Lux |
Electrical Data
| Supply Voltage | 10 … 30 V DC |
| Supply Voltage with IO-Link | 18 … 30 V DC |
| Current Consumption (Ub = 24 V) | 45 mA |
| Switching Frequency | 9.8 kHz |
| Response Time | 51 µs |
| On-/Off-Delay | 0 … 10,000 ms |
| Temperature Drift | < 10 % |
| Temperature Range | -25 … 60 °C |
| Switching Output Voltage Drop | < 2 V |
| Switching Output/Switching Current | 100 mA |
| Short Circuit Protection | yes |
| Reverse Polarity Protection | yes |
| Overload Protection | yes |
| Teach Mode | NT, MT, MT with dynamic readjustment, jump detection, DT, BT, WT |
| IO-Link transmission speed | COM3 |
| Interface | IO-Link V1.1.3 |
| Protection Class | III |
Mechanical Data
| Setting Method | NFC Display |
| Housing Material | Plastic, ABS Plastic, PC Plastic, PA |
| Degree of Protection | IP50 |
| Connection | M8 × 1; 4-pin |
| DIN-Rail mounting | 35 mm |
| Weight | 37 g |
Safety-relevant Data
| MTTFd (EN ISO 13849-1) | 640.47 a |
General Data
| Scope of delivery | 1 × Z1XE001 connector plug and cover cap set 1 × initial start-up instructions 1 × sensor |
Output
| IO-Link | yes |
| NPN NO | yes |
Adjustable parameters
| Output | Push-pull NPN PNP |
| Circuit | inactive Error output NC NC+NO NO |
| Other parameters | 2 switching points Off-delay On-delay Dynamic readjustment Error indicator Error output Filter Hysteresis Switching point Emitted light Sensor localization Adjustable sensor mode Teach mode Multiplex mode |
Standards and certificates
![]() ![]() ![]() ![]() ![]() ![]() ![]() |
Connection Diagram
|
Ctrl. Panel
|
06 = Teach Button
21 = Mode Button 24 = Plus Button 25 = Minus Button 5a = Switching Status Indicator, O1 60 = display 68 = Power LED 6a = Switching Status Indicator, O2 |